NFPA 10 sets how portable fire extinguishers are inspected and maintained. The intervals below come from the 2010 edition as summarized by a state health department. Your jurisdiction may have adopted a different edition.

Monthly visual inspection

At least every 30 days, someone checks location, access, gauge position, seals, damage, corrosion and legibility of instructions. Facility staff can do this. Record the date and the inspector’s initials on a tag, label, checklist or electronic log.

Annual maintenance

A trained technician examines the mechanical parts, the agent and the expelling means at least once a year, and attaches a tag showing the month and year, the technician’s name and the service company.

Six-year maintenance

Stored-pressure dry chemical extinguishers are emptied and internally examined every six years. Some types need more frequent internal exams.

Hydrostatic testing

  • Pressurized water, water mist, CO2 and wet chemical: every 5 years.
  • Dry chemical with stainless steel shells: every 5 years.
  • Dry chemical: every 12 years.

Records

Keep records for monthly inspections, maintenance and hydrostatic tests, ideally for the life of each extinguisher.

Requirements differ by state and city. Your local fire marshal or building department (the “authority having jurisdiction”) has the final say, so confirm with them before acting on anything here.